KL - TZ Series

Energetics | Heat exchangers | KL - TZ Series


COMPACT HEAT EXCHANGER – KL-TZ seriesPressure independent heat exchanger station

Heat transfer stations are designed for systems with a primary heating medium temperature up to 100°C and pressures up to 0.6MPa, it is installed the direct pressure connection to the piping system of the supplied object.



FUNCTIONAL DESCRIPTION

The primary heating water enters through a valve and strainer to transfer station, where it is divided into hot water for heating and exchanger - TV. Before exchanger TV classified mixing circuit, which serves to reduce the temperature of water entering the heat exchanger. Heating water for plate heat exchanger - UT is regulated by two-way control valve-rim and through the back flap is mixed to the heating curve with the return water secondary circuit UT. Heating water circulation system ensures circulation pump with electronically the controlled speed drives.

TV is prepared by direct heating and circulating cold water in the plate heat exchanger. TV temperature is controlled by a control valve with spring-return function at a constant temperature. Circulation from TV enters the headend through the isolating valve, strainer, circulation pump and check valve. Cold water enters the headend through, valves, strainer, check-valve and water meter. Before entering the heated medium to the heat exchanger is fitted with a fuse-ing valve. In exchanger TV cold water (mixed circular and cold water) is heated to the desired temperature (55°C) and via the isolating valve performs in of the supplied object. To balance of the hot water temperature setting and optimum performance values of the control valve it is recommended mount stainless steel buffer tank.


SPECIFICATIONS

  • Max. fluid temperature: 100°C
  • Max. medium pressure
  • Primary: 0.6 MPa
  • Max. power: 2000kW

 

STANDARD EQUIPMENT STATION

  • Plate heat exchanger: SWEP, Alfa Laval
  • Control valves: LDM, Siemens
  • Taps: BROEN
  • Pumps: Grundfos, Wilo

DESIGN support construction consists of a steel frame welded from thin sections, presented in which it is firmly held their own machinery. Primary distribution pipe and pipe sections UT is steel class. 11, duct section TV is steel class 17th The station is designed and constructional solution, the minimized noise and vibration operation.


Station Control Stations can be mounted control technology to the extent of the customer's choice. Simple controllers provide fully autonomous operation of the stations, including the choice of several time programs, setting equitherm dependencies with limited communication with the dispatching center. Programmable controllers offer a wide range of compact control at substations. Well-chosen programs can be up to optimize operation of the stations. Programmable controllers allow two-way communication with the control center, traffic monitoring, reporting, emergency situations, etc.


STANDARD SERIES PERFORMANCE, DIMENSIONS ARE ONLY INDICATIVE | 90/60-80/60°C - Winter | 65/35-10/55°C - Summer

Pressure | Prim / UT / TV | PN25/6/10

Performance

Dimensions

The dimensions of the pipe (mm)

UT (kW)

TV (kW)

Length L(mm)

Height H(mm)

Width V(mm)

Prim tot

sek UT

prime TV

cirkul TV

TZ – 50/140

50

140

1200

1700

500

32

25

25

25

TZ  – 90/230

90

230

1200

1700

500

40

32

32

25

TZ  – 120/310

120

310

1500

1800

500

50

40

40

32

TZ  – 190/510

190

510

1700

1900

650

65

50

50

40

TZ  – 340/840

340

840

1900

1900

650

80

65

65

50

TZ  – 470/840

470

840

2000

1900

700

80

80

65

50

TZ  – 810/840

810

840

2100

2100

750

80

100

65

50


DIAGRAM diagram and used components can be replaced by the customer. Stations are supplied without pipe insulation that can be reordered, possibly in the plating compact. For the less accessible places it is possible to produce an atypical involvement and adapt best compact a defined space. Overall design of substations, including drawings, it is always consulted with the chief engineer and the client.





P – primar

U - Central heating

T - Domestic hot water

S – cold water

C – circulation

D – Topping

N – Charging of TV

-1 – Heat medium

-2 – Cold medium

0 - Plate heat exchanger

1 - Shut-off valves

2 – Filters

3 – Calorimeter

4 – Barometer

5 – Thermomanometer

6 –Pump

7 – Regulating valve

8 - Check valves

9 - Check valves

10 – Safety valve

11 - Heat Meter

12 - Water-gauge

13 - Flow Controllers

14 - Vent valve cars.

15 - Drain valve

16 - Regulator diferential pressure

17 – Water line

18 - Misc



















Pronađite nas na: